SECTION 5 - TECHNICAL DATA
Form 201.47-ICOM1
Issue date: 17/11/2022
All dimensions - in. (mm)
YVAA
Model
A B C1 C2 D D2
E-nozzle
size
Figure
Water
volume gal
(l)
Minimum
chilled water
ow rate
GPM (l/s)
Maximum
chilled water
ow rate
GPM (l/s)
0199/0699
1603.6
(63.13)
915.0 (36.02)
1073.3
(42.26)
1117.6 (44.00)
366.7
(14.44)
666.1 (26.22) 5 A 31 (120) 130 (8.2) 860 (54)
0234/0824
1603.6
(63.13)
915.0 (36.02)
1073.3
(42.26)
1117.6 (44.00)
366.7
(14.44)
666.1 (26.22) 5 A 44 (170) 130 (8.2) 860 (54)
0261/0921
1583.6
(62.35)
895.0 (35.24)
1117.6
(44.00)
1117.6 (44.00)
373.0
(14.69)
703.0 (27.68) 5 A 44 (170) 220 (14) 1040 (66)
0216/0756
1034.4
(40.72)
3696.8
(145.54)
1077.3
(42.41)
1117.6 (44.00)
353.1
(13.90)
678.1 (26.70) 5 A 31 (120) 130 (8.2) 580 (37)
0226/0796
1603.6
(63.13)
2032.0
(80.00)
1073.3
(42.26)
1117.6 (44.00)
366.7
(14.44)
666.1 (26.22) 5 A 44 (170) 130 (8.2) 860 (54)
0259/0919
1603.6
(63.13)
2032.0
(80.00)
1073.3
(42.26)
1117.6 (44.00)
366.7
(14.44)
666.1 (26.22) 5 A 44 (170) 130 (8.2) 860 (54)
0266/0936
1583.6
(62.35)
2012.0
(79.21)
1117.6
(44.00)
1117.6 (44.00)
372.9
(14.68)
703.0 (27.68) 6 A 52 (200) 220 (14) 1040 (66)
0219/0769
1034.4
(40.72)
4813.8
(189.52)
1077.3
(42.41)
1117.6 (44.00)
353.1
(13.90)
678.1 (26.70) 4 A 31 (120) 130 (8.2) 580 (37)
0229/0809
1603.6
(63.13)
3149.0
(123.98)
1073.3
(42.26)
1117.6 (44.00)
366.7
(14.44)
666.1 (26.22) 5 A 44 (170) 130 (8.2) 860 (54)
0264/0924
1603.6
(63.13)
3149.0
(123.98)
1073.3
(42.26)
1117.6 (44.00)
366.7
(14.44)
666.1 (26.22) 5 A 44 (170) 130 (8.2) 860 (54)
0246/0866
1603.6
(63.13)
3149.0
(123.98)
1073.3
(42.26)
1117.6 (44.00)
366.7
(14.44)
666.1 (26.22) 5 A 52 (200) 130 (8.2) 860 (54)
0269/0949
1583.6
(62.35)
3129.0
(123.19)
1117.6
(44.00)
1117.6 (44.00)
372.9
(14.68)
703.0 (27.68) 6 A 52 (200) 220 (14) 1040 (66)
0324/1134
1583.6
(62.35)
3129.0
(123.19)
1117.6
(44.00)
1117.6 (44.00)
372.9
(14.68)
703.0 (27.68) 6 A 52 (200) 220 (14) 1040 (66)
0294/1034
1583.6
(62.35)
3129.0
(123.19)
1117.6
(44.00)
1117.6 (44.00)
372.9
(14.68)
703.0 (27.68) 6 A 52 (200) 220 (14) 1040 (66)
0331/1161
1583.6
(62.35)
4245.0
(167.13)
1117.6
(44.00)
1117.6 (44.00)
372.9
(14.68)
703.0 (27.68) 6 A 52 (200) 220 (14) 1040 (66)
0306/1076
1583.6
(62.35)
4245.0
(167.13)
1117.6
(44.00)
1117.6 (44.00)
372.9
(14.68)
703.0 (27.68) 6 A 52 (200) 220 (14) 1040 (66)
0309/1089
1583.6
(62.35)
5363.0
(211.14)
1117.6
(44.00)
1117.6 (44.00)
372.9
(14.68)
703.0 (27.68) 6 A 52 (200) 220 (14) 1040 (66)
0334/1174
1583.6
(62.35)
5363.0
(211.14)
1117.6
(44.00)
1117.6 (44.00)
372.9
(14.68)
703.0 (27.68) 6 A 52 (200) 220 (14) 1040 (66)
0491/1731
1501.5
(59.11)
4198.9
(165.31)
917.6
(36.13)
1317.6
(51.87)
393.7
(15.50)
783.7 (30.85) 6 B 52 (200) 270 (17) 1210 (76)
0361/1271
1501.5
(59.11)
4163.9
(163.93)
917.6
(36.13)
1317.6
(51.87)
393.7
(15.50)
703.0 (27.68) 6 B 52 (200) 270 (17) 1040 (66)
0391/1381
1501.5
(59.11)
4198.9
(165.31)
917.6
(36.13)
1317.6
(51.87)
393.7
(15.50)
703.0 (27.68) 6 B 52 (200) 270 (17) 1040 (66)
0456/1606
1501.5
(59.11)
6403.9
(252.12)
917.6
(36.13)
1317.6
(51.87)
393.7
(15.50)
783.7 (30.85) 6 B 52 (200) 270 (17) 1210 (76)
0399/1409
1501.5
(59.11)
6438.9
(253.50)
917.6
(36.13)
1317.6
(51.87)
393.7
(15.50)
703.0 (27.68) 6 B 52 (200) 270 (17) 1040 (66)
0469/1649
1501.5
(59.11)
7520.9
(296.10)
917.6
(36.13)
1317.6
(51.87)
393.7
(15.50)
783.7 (30.85) 6 B 52 (200) 270 (17) 1210 (76)
0459/1549
1501.5
(59.11)
4198.9
(165.31)
917.6
(36.13)
1317.6
(51.87)
393.7
(15.50)
783.7 (30.85) 6 B 52 (200) 270 (17) 1210 (76)
Table 9 - Optional three-pass inlet/outlet connections (cont'd)
Note: The minimum and maximum ow rates listed here only represent the span of ows for a group of available evaporator options. Actual
chiller ow rates vary based on specic evaporator congurations. The application datasheet or nameplate must be referenced for specic ow
limits for every chiller.
Note: Minimum Chilled Water Flow Rate is for full load selections; Variable Primary Flow ratings as low as 50% of the minimum are
permitted. Glycol limits are higher. Contact your Johnson Controls Sales O󰀩ce for ratings and further information.