EasyManua.ls Logo

Zennio DALIBOX Interface 64/32 - Page 16

Zennio DALIBOX Interface 64/32
71 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
DALIBOX Interface 64/32
http://www.zennio.com Technical Support: http://support.zennio.com
16
Heartbeat (Periodical Alive Notification) [enabled/disabled]: this
parameter lets the integrator incorporate a one-bit object to the project
(“[Heartbeat] Object to Send ‘1”) that will be sent periodically with a value
of “1” to notify that the device is still working (still alive).
Figure 3. Heartbeat.
Note: The first sending after download or bus failure takes place with a delay
of up to 255 seconds, to prevent bus overload. The following sendings
match the period set.
Detect Collisions after Download [enabled/disabled]. Regardless of the
value of this parameter, this function can be activated or deactivated by
object “Collisions Detection”, which is always visible.
Standard bit timing [enabled/disabled]: allows enabling or disabling the
manual configuration of the bit detection time. The standard value set by
default is 500 μs.
Maximum time for one-bit phase [500…650]: sets the new
threshold value.
Note: preserving the standard threshold is highly encouraged, unless
intending to connect very specific ballasts that may require modifying it.
Figure 4. Standard Bit Timing.
Manual Control Lock Object [enabled/disabled]: when enabled, 1-bit
object “Manual Control Lock Object” turns visible, as well as two more
parameters: