EasyManua.ls Logo

Zennio DALIBOX Interface 64/32 - Status Objects

Zennio DALIBOX Interface 64/32
71 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
DALIBOX Interface 64/32
http://www.zennio.com Technical Support: http://support.zennio.com
40
2.5.5 STATUS OBJECTS
DALIBOX Interface 64/32 provides different objects that report the current dimming state
of the output group:
A one-bit object (On/Off).
A one-byte object, which indicates the dimming level (in percentage).
ETS PARAMETERISATION
After enabling this function, the following options will be available in the “Status Objects”
tab:
Figure 17. Status Objects
Send On/Off Status [enabled/disabled]: enables sending a one-bit object
(“[Group n] On/Off (Status)”) whenever the group is switched off (“0”) or on
(“1”).
Send Dimming Status [enabled/disabled]: enables a one-byte object
(“[Group n] Dimming Value (Status)”) that will be sent with the current
dimming value of the group (between 0% and 100%) whenever it changes.
Enabling this parameter brings up an addition one:
Sending Period [0…255] [s]: defines the sending cycle time of the status
object during a dimming process. If it is set to “0”, the dimming status will be
sent only at the end of the dimming process.