DALIBOX Interface 64/32
http://www.zennio.com Technical Support: http://support.zennio.com
49
Initial Status: sets the desired initial state of the group:
[Last Value]: when the KNX bus power is restored, the group will recover
the dimming state previous to the bus failure. Note that this option has no
effect after a download (the group will remain off).
[Off]: the group will always start switched off.
[Defined Value]: the group will start at a specific dimming level, configured
in Value [0…100] [%].
Send Status [enabled/disabled]: if enabled, the status objects will be sent to
the bus at the start-up to inform about the initial state of the group. This requires
that the status objects have been enabled (see section 2.5.5).
Delay [0…255] [s]: sets a delay before performing this sending.
2.5.10 MODES
DALIBOX Interface 64/32 implements two special operation options named as Burn-in
mode and Auto-Off mode, each of which is explained in detail next.
2.5.10.1 AUTO OFF MODE
The Auto Off mode allows an automatic switch-off of the group if it is found to be steady
(i.e., without receiving further dimming orders) under a certain dimming value or
threshold for at least a certain amount of time (configurable).
This function will not take place while any of the following is active:
Power supply error.
Short-circuit error.
Test On mode.
Lock.
Burn-in mode.
Timers.