downloading the new parameterisation or maintained in case it had already
been performed (either through previous parameter downloads or by means of
the on-board controls and display).
In case this option is left disabled, the following parameter is shown:
➢ Enable ECG N [enabled/disabled]: sets which ballasts will remain enabled.
Note that, although they may have been assigned a group previously, they
will be shown under the “No group” tab (see section 2.4).
On the other hand, if enabled, the following parameter is shown:
➢ ECG N Group Assignment [enabled/disabled]: sets which ballasts will
remain enabled and, optionally, the group assigned to each of them:
• “–”: ballast N is disabled.
• No Group: ballast N is enabled but has no group assigned.
• Group Y: ballast N is enabled and associated to group Y.
Note: groups 17 – 32 are one-ballast groups.
Important: any groups being assigned to ballasts must also be explicitly enabled. See
section 2.3.
A specific sub-tab will be available per ballast under the tab of the group the ballast
belongs to. See section 2.5.2.