44
Figure 20. Simple Timer
On Duration [0…255] [s/min]: sets the time the group will remain on. The value
“0” will disable the automatic switch-off, thus making the group remain on.
On Delay [0…255] [s/min]: sets a delay after the reception of value “1through
object “[Group n] Simple Timer.
Off Delay [0…255] [s/min]: sets a delay after the reception of value “0” through
object “[Group n] Simple Timer”.
Action in Case of Retriggering [Nothing / Restart / Multiply] sets the action to
be performed in case the value “1” is received several times.
On Value [1…100] [%]: sets the specific dimming percentage to be applied to
the group during the “on” stage.
Dimming Time [At Once / Dimming Time 1 / Dimming Time 2 / Dimming Time
3].