2.5.7.2 FLASHING
The flashing function requires configuring the following options:
On Duration: length of each “On” stage during the sequence.
Off Duration: length of each “Off” stage during the sequence.
Repetitions: number of iterations of the sequence.
On Value: dimming level to be applied to the group during the “On” stages.
Final Value: dimming level to be applied to the group after the last repetition
or after the reception.
PARAMETRIZACIÓN ETS
Once the flashing function has been enabled, the “[Group n] Flashing” one-bit object
will turn visible in order to let triggering an On-Off-On… sequence by sending it the value
“1”, as well as interrupting it by sending it the value “0” The options for this function are
the following:
Figure 21. Flashing
On Duration [1…255] [s/min]: sets the length of each “On” stage.
Off Duration [1…255] [s/min]: sets the length of each “Off” stage.
Repetitions [0…100]: sets the number of iterations of the sequence. A value
of “0” (default option) causes an endless repetition, until an order to interrupt
the sequence is received.