EasyManua.ls Logo

3S MP 100 - Troubleshooting

Default Icon
43 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
29
Remove the O-rings from pilot case.
[See figures below]
Replacement
Place the new O-rings to the pilot case.
In case of Single- action, make sure the shim is placed.
If you lost the shim, use the new shim included in the repair kit.
Caution! Different numbers of the O-rings and shim are used for
Single- action and Double- action.
Please replace them referring to the above figures.
Place the new pilot relay unit to the pilot case with the four M4 Phillips screws.
Be careful not to drop the O-ring during work.
After the installation of the pilot relay unit, start Auto-tuning.
Be sure to check the noise during Auto-tuning.
If the noise is loud, Check the position of O-rings and reinstall the pilot unit.
Mount the pilot case cover with the three M5 Phillips screws.
10. Troubleshooting
Issue Cause Action
LCD doesn’t display
Bad connection Tighten terminal
Wrong with + / - wiring Re wiring
Breakdown of LCD Replace circuit board
Input signal is less than 3.8 mA
Input signal is more than
3.8
mA
Not working
Clogging of fixed orifice Replace fixed orifice
Device is in manual mode
Change to
auto
mode
Settings were changed
Re
tuning
Broken Wires Replace broken wires
Ruptures of diaphragm
Replace
pilot relay
Lack of supply air pressure
Supply prescribed air
pressure
Shift the set point
Wear on the levers
Levers have worked loose
Replace levers
Re
-
tightening
Sensor was damaged Replace sensor
Continuous hunting
Not stabilized
Heavy overshooting
Mismatching in PID
Re-tuning
Adjust manually
Clogging of fixed orifice Replace fixed orifice
Poor linearity The positioner is installed in poor posture
Reinstall positioner
Refer to
4. Installation