34
IECEx Flame-proof
Ex
The symbol Ex (indication by IEC)
For flameproof enclosure
Gb
T6
ⅡC
Equipment Protection Level (indication by IEC)
Ignition temperature of gas or vapor in the atmosphere is over 85℃
Atmosphere of Group ⅡC gases
Flame-proof equipment may be installed, with targeted gases, in a hazardous area in Zone 1 or 2.
Flame-proof equipment shall not be installed in a hazardous area in Zone 0.
NEPSI Flame-proof
Ex
db
The symbol Ex (indication by IEC)
For flameproof enclosure
Gb
T6
ⅡC
Equipment Protection Level (indication by IEC)
Ignition temperature of gas or vapor in the atmosphere is over 85℃
Atmosphere of Group ⅡC gases
Flame-proof equipment may be installed, with targeted gases, in a hazardous area in Zone 1 or 2.
Flame-proof equipment shall not be installed in a hazardous area in Zone 0.
ATEX Flame-proof
Equipment Group(indication by ATEX)
Gb
T6
For flameproof enclosure
ⅡC
Atmosphere of Group ⅡC gases
The symbol Ex (indication by IEC)
Group for explosive atmospheres (indication by ATEX)
Ignition temperature of gas or vapor in the atmosphere is over 85℃
Equipment Protection level (indication by IEC)
2G
Ex
Flame-proof equipment may be installed, with targeted gases, in a hazardous area in Zone 1 or 2.
Flame-proof equipment shall not be installed in a hazardous area in Zone 0.
(2) Environmental Conditions
The temperature range for MP100 positioner of Flame-proof type is certified at an ambient temperature
range from -20 to +60.
This is also indicated on the nameplate.
When using the equipment, please operate in the ambient temperature range.
NEPSI Flame-proof
Do not use in environments where aluminum alloy is corroded.