38
【IECEx, ATEX Flame-proof】
For Installation, follow the EN/IEC60079-14.
For wiring connection port of positioner, use cable gland and blind plug corresponding to Ex d IIC
approved. Please use the cable gland is selected with the correct size to fit the cable used.
Apply a sealant to the threads of the connection port for waterproofing.
For the wiring, please conduct in accordance with national legislation of the country to be used.
When connecting the earth, the cable lug shall be connected between spring washer and plain washer.
Please ensure to connect to the earth ground by wire cross section of 4mm
2
or more with ring terminal
etc.
【NEPSI Flame-proof】
For Installation, follow the GB3836.13-2013, GB/T3836.15-2017, GB/T3836.16-2017 and GB50257-
2014.
For wiring connection port of positioner, use cable gland and blind plug corresponding to Ex db IIC
NEPSI approved. Please use the cable gland is selected with the correct size to fit the cable used.
Apply a sealant to the threads of the connection port for waterproofing.
For the wiring, please conduct in accordance with national legislation of the country to be used.
When connecting the earth, the cable lug shall be connected between spring washer and plain washer.
Please ensure to connect to the earth ground by wire cross section of 4mm
2
or more with ring terminal
etc..
【KOSHA Flame-proof】
For wiring connection port of positioner, use cable gland and blind plug corresponding to ExdIIC
approved. Please use the cable gland is selected with the correct size to fit the cable used.
Apply a sealant to the threads of the connection port for waterproofing.
For the wiring, please conduct in accordance with national legislation of the country to be used.
When connecting the earth, the cable lug shall be connected between spring washer and plain washer.
Please ensure to connect to the earth ground by wire cross section of 4mm
2
or more with ring terminal
etc..