EasyManuals Logo

AAON RN Series Installation, Operation & Maintanance Manual

AAON RN Series
116 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #49 background imageLoading...
Page #49 background image
49
Wire control signals to the unit’s low
voltage terminal block located in the
controls compartment.
If any factory installed wiring must be
replaced, use a minimum 105°C type AWM
insulated conductors.
Variable Speed Compressors
Variable speed compressors with VFD
speed control are available on 55, 65 and 75-
140 ton units. Variable speed compressors
should not be operated outside the factory
determined frequency range. The factory
determined compressor VFD frequency
range is given below in Table 7.
Table 7 - Variable Speed Compressor VFD
Frequency Range
Model (RN-)
Compressor VFD
Range (Hz)
208V, 230V and 380V Units
055, 065 & 075-140
35-60 Hz
460V and 575V Units
055, 065, 075, 090,
120, 130
35-75 Hz
105, 140
35-60 Hz
Thermostat Control Wiring
If a thermostat is used for unit control,
thermostat should be located on an inside
wall 4-5 feet above the floor where it will
not be subjected to drafts, sun exposure, or
heat from electrical fixtures of appliances.
Control wiring must deliver adequate
voltage to components to assure proper
operation. Control voltage returning from
controller circuit must be a minimum of 21
VAC. To assure proper wiring use the
following chart to determine the allowable
wiring distances.
Table 8 - Control Wiring
Wire Size (Stranded)
- Copper Conductors
Only
Total Wire Distance
Allowable
20 AWG
200 ft
18 AWG
350 ft
16 AWG
500 ft
14 AWG
750 ft
12 AWG
1250 ft
No variable speed compressor shall
operate below 35 Hz. Operating
variable speed compressors outside
the frequency range specified in this
manual voids all warranties and may
result in compressor failure.
CAUTION
Scroll compressors are directional
and will be damaged by operation in
the wrong direction. Low pressure
switches on compressors have been
disconnected after factory testing.
Rotation should be checked by a
qualified service technician at startup
using suction and discharge pressure
gauges and any wiring alteration
should only be made at the unit
power connection.
CAUTION
Rotation must be checked on all
MOTORS AND COMPRESSORS of
three phase units. Supply fan,
exhaust fan, return fan, and
condenser fan motors should all be
checked by a qualified service
technician at startup and any wiring
alteration should only be made at the
unit power connection.
CAUTION

Table of Contents

Other manuals for AAON RN Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AAON RN Series and is the answer not in the manual?

AAON RN Series Specifications

General IconGeneral
CategoryHeat Pump
HSPFUp to 10.0
RefrigerantR-410A
Compressor TypeScroll
EfficiencyHigh
SeriesRN
Voltage Options208-230/460V
Unit WeightVaries with model
DimensionsVaries with model

Related product manuals