30
RSMD-CM Technical Guide
TROUBLESHOOTING
Head Pressure Transducer
Table 7: Head Pressure Transducer Chart
If you suspect there is a problem related to the Head Pressure
Transducer, voltage and pressure readings can be taken at the
HP terminal. See Table 7, this page.
Head Pressure Transducer Chart
Voltage Pressure Voltage Pressure
0.5 0 2.6 350
0.6 17 2.7 367
0.7 33 2.8 384
0.8 50 2.9 400
0.9 67 3.0 417
1.0 83 3.1 434
1.1 100 3.2 450
1.2 117 3.3 467
1.3 133 3.4 484
1.4 150 3.5 500
1.5 167 3.6 517
1.6 183 3.7 534
1.7 200 3.8 550
1.8 217 3.9 567
1.9 233 4.0 584
2.0 250 4.1 600
2.1 267 4.2 617
2.2 283 4.3 634
2.3 300 4.4 650
2.4 317 4.5 667
2.5 334