29VCCX2 Controller Technical Guide
INPUTS AND OUTPUTS
User Congurable Relay Outputs
USER-CONFIGURABLE RELAY OUTPUTS
NO. RELAY DESCRIPTIONS DETAILS
1 Cooling Stage Congured for each xed stage of cooling (except heat pump compressor).
2 Heating Stage Congured for each xed stage of heating.
3 Aux Heat Congured for a xed stage of aux heat in a heat pump unit.
4 Emergency Heat Congured for a xed stage emergency heat in a heat pump unit.
5 Mod Heat Enable Congure if a 0-10 VDC modulating heat source needs a relay to enable it.
6 Mod Cool Enable Congure if a 0-10 VDC modulating cool source needs a relay to enable it.
7 Morning Warm-Up /
Cool-Down (VAV Boxes)
Congure (1) relay for morning Warm-Up/Cool-Down when non-Orion VAV/Zone Controllers are used.
8 Reheat Congure (1) relay for on/o reheat when used.
9 Preheat Congure for preheat operation.
10 Low Ambient Congure for low ambient operation.
11 Exhaust or Return Fan Congure (1) relay for enabling exhaust or return fan when building pressure control is used.
12 Economizer Active If congured, this relay will energize if unit is in Economizer Mode and the damper has moved 5% above its
Economizer Minimum Setpoint position or if the damper moves above a user-adjustable position setpoint.
13 Heat Wheel Congure (1) relay that turns heat wheel on when in occupied operation and turns heat wheel o when in
Economizer Mode.
14 Occupied Active If congured, this relay will energize whenever the unit is in the Occupied Mode.
15 Override Active If congured, this relay will energize anytime the space sensor push-button override is active.
16 Alarm Active If congured, this relay will energize anytime a VCCX2 alarm is active.
17 A1 Comp Run Status Will enable when the RSM A1 compressor activates.
18 A2 Comp Run Status Will enable when the RSM A2 compressor activates.
19 B1 Comp Run Status Will enable when the RSM B1 compressor activates.
20 B2 Comp Run Status Will enable when the RSM B2 compressor activates.
21 Condenser Pump If congured, this relay will energize when the unit requires the evaporative condenser to be enabled.
22 Sump Heater If congured, this relay will energize when the unit requires the sump heater to be enabled.
23 Sump Pump Drain If congured, this relay will energize when the unit requires the sump pump drain to be enabled.
Table 10: User-Congurable Relay Outputs