EasyManua.ls Logo

AAON VCCX2 - Table 27: Settings Screens; Table 28: Status Screens

AAON VCCX2
95 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
68VCCX2 Controller Technical Guide
APPENDIX B: LCD SCREENS
Screen Descriptions
Settings Screens
Refer to the following map when navigating through the Settings
Screens. From the Settings Screen, press <ENTER> to scroll through
the screens.
SETTINGS SCREENS
Screen Text Description
Settings Settings screens.
Unit ID#
Addr 59
Unit address ID. Valid range is 1-59. Default is 59.
Once the cursor is under a eld, use the <UP> and
<DOWN> arrow keys to select a number between
0 and 9.
485-Baud
Hi-Speed
485 baud rate speed. Valid options are Lo-Speed or
Hi-Speed. Default is Hi-Speed. Use the <UP> and
<DOWN> arrow keys to select the options.
MAC Addr
1
BACnet. Current MAC address. Valid range is
0-127. Default is 1. Once the cursor is under a
eld, use the <UP> and <DOWN> arrow keys to
select a number between 0 and 9.
DeviceID
XXXXX
BACnet. Current device ID. A device ID with up to
seven digits can be entered. Once the cursor is
under a eld, use the <UP> and <DOWN> arrow
keys to select a number between 0 and 9.
MSTPBaud
XXXXX
BACnet. Current baud rate. Valid options are 9600,
19200, 38400, 57600, 76800. Default is 38400.
EBUS
XX Speed
EBUS communication speed. Valid options are Hi
Speed and Lo Speed. Default is Hi Speed.
Table 27: Settings Screens
Status Screens
Refer to the following map when navigating through the Status
Screens. From the Status Screen, press <ENTER> to scroll through
the screens.
STATUS SCREENS
Screen Text Description
Status Status screens.
OperMode Operation mode. Options are:
UNOCCUPY (Unoccupied)
OCCUPIED
OVERRIDE
HOL UNOC (Holiday unoccupied)
FRC OCC (Force occupied)
FRC UNOC (Force unoccupied)
REM OCC (Remote occupied)
ZONEHEAT (Zone heat)
ZONECOOL (Zone cool)
ZONE OVR (Zone override)
HvacMode HVAC mode. Options are:
OFF
VENT
COOL
HEAT
VENT RH
COOL RH
HEAT RH
WARMUP
PURGE
DEFROST
COOLDOWN
Spc Temp
XX.X°
Space temperature.
Spc RH
X.X %
Space humidity. 0.00% - 100%.
SA Temp
XX.X°
Supply air temperature.
RA Temp
XX.X°
Return air temperature.
OA Temp
XX.X°
Outdoor air temperature.
OA RH
X.X %
Outdoor air humidity. 0.00% - 100%.
CO2Level
X ppm
Carbon dioxide level. 0.00 ppm to 5000 ppm.
Table 28: Status Screens