9 Specification
9.1 Functional specifications
9.1.1 Measuring range limits and span limits
Sensor code Measuring range upper
limit (URL)
Measuring range lower
limit (LRL)
Model 261GS
Minimum measuring span
Model 261GS
Gauge pressure
Model 261AS
Absolute pressure
C 6 kPa
60 mbar
24 inH
2
O
-6 kPa
-60 mbar
24 inH
2
O
0,3 kPa
3 mbar
1,2 inH
2
O
0,3 kPa
3 mbar
2,25 mm Hg
F 40 kPa
400 mbar
160 inH
2
O
-40 kPa
-400 mbar
-160 inH
2
O
2 kPa
20 mbar
8 inH
2
O
2 kPa
20 mbar
15 mm Hg
L 250 kPa
2500 mbar
1000 inH
2
O
0 abs 12,5 kPa
125 mbar
50 inH
2
O
12,5 kPa
125 mbar
93,8 mm Hg
D 1000 kPa
10 bar
145 psi
0 abs 50 kPa
500 mbar
7,25 psi
50 kPa
500 mbar
375 mm Hg
U 3000 kPa
30 bar
435 psi
0 abs 150 kPa
1,5 bar
21,7 psi
150 kPa
1,5 bar
21,7 psi
R 10000 kPa
100 bar
1450 psi
0 abs 500 kPa
5 bar
72,5 psi
500 kPa
5 bar
72,5 psi
V 60000 kPa
600 bar
8700 psi
0 abs 3000 kPa
30 bar
435 psi
-
IMPORTANT (NOTICE)
The measuring range lower limit (LRL) for model 261AS is absolute 0 for all measuring ranges.
Change from one to two colu mns
9.1.2 Span limits
Maximum span = measuring range upper limit (URL)
To optimize performance characteristics, it is recommended
that you select the transmitter sensor code with the lowest
turn down ratio.
TURNDOWN = Upper range limit / set span
9.1.3 Zero suppression and elevation
The zero position and span can be set to any value within the
measuring range limits listed in the table if:
— Set span ≥ minimum span
9.1.4 Damping
Configurable time constant between 0 and 60 s.
This is in addition to the sensor response time, and can be
adjusted via the optional LCD indicator, handheld terminal, or
PC user interface.
9.1.5 Warm-up time
Ready for operation as per specifications in less than 10 s with
minimum damping.
9.1.6 Insulation resistance
>100 MΩ at 500 V DC (between terminals and ground).