2600T Series Pressure transmitters | OI/266/FF/ADD-EN Rev. B 19
– Line on side H plugged
– Line on side L plugged
– Both lines H and L plugged
– An undefined line plugged
In this case also the device diagnosis is affected setting the bit Pild_Output in the RB_MAINTENANCE_ACTIVE and the specific
bit of the above detailed 4 info in the RB_EXTENDED_ACTIVE.
When one of the above conditions has been detected, there is the possibility that the process variables in output from the PRTB
continue to be produced with GOOD status.
In this way the AI blocks receiving in input the variables from the PRTB works normally and the operator could have not evidence of
the wrong conditions. For this reason it is possible make a choice in order to decide to affect or not the PRTB variables when the
plugging conditions have been detected. This selection is possible with the ADTB_PILD_AFFECT_PV variable. When it is selected
to true, and the Plugging conditions are detected, the GOOD status that would be produced in output for the
PRTB_PRIMARY_VALUE, PRTB_SECONDARY_VALUE, PRTB_TERTIARY_VALUE, PRTB_QUATERNARY_VALUE are all
forced to BAD status. The PILD algorithm loses the train every time it is switched off. The algorithm is switched off automatically for
every error condition, except when the pressure violates the maximum pressure deviation and the retrain is selected.
Historical/statistical info
From this block can be also read the Minimum and Maximum values measured by the transducer of Pressure, Static Pressure and
Sensor Temperature plus the total working time and the number of device power cycles. These information can allow the user to do
detailed/specific diagnostic analysis and evaluations.