2600T Series Pressure transmitters | OI/266/FF/ADD-EN Rev. B 51
Idx Parameter Data Type Size Storage Description / Range / Selections / Note
21 BIAS_IN_1 RW S FLT 4 S
The constant to be added to IN_1
22 GAIN_IN_1 RW S FLT 4 S
The constant to be multiplied times (IN_1 + Bias)
23 BIAS_IN_2 RW S FLT 4 S
The constant to be added to IN_2
24 GAIN_IN_2
RW
S FLT 4
S
The constant to be multiplied times (IN_2 + Bias)
25 BIAS_IN_3 RW S FLT 4 S
The constant to be added to IN_3
26 GAIN_IN_3 RW S FLT 4 S
The constant to be multiplied times (IN_3 + Bias)
27 COMP_HI_LIM RW S FLT 4 S
The high limit imposed on the PV compensation term. Expressed in PV_SCALE Unit Code
28 COMP_LO_LIM RW S FLT 4 S
The low limit imposed on the PV compensation term. Expressed in PV_SCALE Unit Code
29 ARTH_TYPE RW S U8 1 S
The identification number of the arithmetic algorithm
1 Flow Compensation, Linear
2 Flow Compensation, Square Root
3 Flow Compensation, Approximate
4 BTU Flow
5 Traditional Multiple Divide
6
Average
7
Traditional Summer
8
Fourth Order Polynomial
9
Simple HTG compensated Level
30 BAL_TIME RW S FLT 4 S
Acceptable value: OUT_SCALE +/- 10%
Expressed in OUT_SCALE Unit
The specified time for the internal working value of bias to return to operator set bias. Also
used to specify the time constant at which the integral term will move to obtain balance
when the output is limited and the mode is AUTO, CAS, or RCAS. Expressed in seconds
31 BIAS RW S FLT 4 N Expressed in OUT_SCALE Unit The bias value used in computing the function block output
32 GAIN RW S FLT 4 S 0 or > 0 Dimensionless value used by the block algorithm in calculating the block output
33 OUT_HI_LIM RW S FLT 4 S
Acceptable value: OUT_SCALE +/- 10%
Expressed in OUT_SCALE Unit
Limits the maximum output value.
34 OUT_LO_LIM RW S FLT 4 S Limits the minimum output value.
35 UPDATE_EVT R R DS-73 14 D This alert is generated by any change to the static data
36 BLOCK_ALM RW R DS-72 13 D
The block alarm is used for all configuration, hardware, connection failure or system problems in the block. The cause of the alert is entered
in the subcode field. The first alert to become active will set the Active Status in the status parameter. As soon as the Unreported status is
cleared by the alert reporting task, another block alert may be reported without clearing the Active Status, if the subcode has changed