24 OI/266/LowP-EN Rev.A | 2600T Series Pressure transmitters
9 Error messages
C088.030
Input Simulation
Active
The Sensor Temperature Value produced
in output is derived by the value simulated
in input
Use a HART configurator (DTM - Hand held) to place
device back in to normal operating mode (Remove
the input simulation)
no effect
M020.042 Replace Info
The Electronics or the Sensor have been
changed but the replacement operation
has not been executed
The replacement operation must be executed: Move
the SW 1 of the electronics in position 1 = Enable
replace mode -Select the SW 2 the element that has
been changed between new Sensor or new
electronics -Power Cycle the device -Move the SW 1
of the electronics in position 0
no effect
C090.033
Analog Output
Fixed
The analog output for the Primary Variable
is derived by the value simulated in input.
Use a HART configurator (DTM - Hand held) to place
device back in to normal operating mode (Remove
the analog output simulation)
no effect
— Operation related error messages
Error message Tx LCD message Possible cause Suggested action Tx response
M022.041
Electronic
Temperature Out of
Limits
The Electronics temperature is out of its lower
acceptable limit. The circuitry for the sampling of
the Electronics Temperature has failed.
The Electronics should be replaced as soon as
possible.
no effect
M022.041
Electronic
Temperature Out of
Limits
The Electronics temperature is out for its Higher
acceptable limit. The circuitry for the sampling of
the Electronics Temperature has failed.
The Electronics should be replaced as soon as
possible.
no effect
— Process related error messages.
Error message Tx LCD message Possible cause Suggested action Tx response
F104.032 Pressure Overrange
This effect could be produced by other equipment on the
process, (valves…..). Exceeding the pressure range can
cause reduced accuracy or mechanical damage to the
diaphragm material and may require calibration/replacement.
The compatibility of pressure transmitter
model and process conditions has to be
checked. A different transmitter type could
be required
no effect
F102.004 P-dP Out Of Limits
The measurement range has not been correctly calculated
OR an incorrect transducer model has been selected.
The compatibility of pressure transmitter
model and process conditions has to be
checked. Probably a different transmitter
type is required.
no effect
F100.005
Static Pressure Out
of Limits
The static pressure of the process exceeds the limit of the
sensor. Exceeding the Static Pressure can reduce accuracy,
mechanically damage the diaphragm and may require
calibration/replacement. An incorrect transducer model
could have been selected.
The compatibility of pressure transmitter
model and process conditions has to be
checked. Probably a different transmitter
type is required.
no effect
S054.006
Sensor Temperature
Out of Limits
The temperature of the process environment affects the
pressure transmitter; Excess temperature can reduce
accuracy, degrade device components and may require
calibration/replacement.
The compatibility of pressure transmitter
model and process conditions has to be
checked. A different installation type could
be required e.g. use of remote seals.
no effect
S052.031
Max Working
Pressure Exceeded
The static pressure of the process exceeds the max working
Pressure supported by the transmitter. Exceeding the Max
Working Pressure can mechanically damage the process
connections (flanges, pipes….) and/or be dangerous
The compatibility of pressure transmitter
model and process conditions has to be
checked.
no effect
F098.034
Analog Output
Saturated
The analog output for the Primary Variable is beyond its Low
scaling limit and no longer represents the true applied
process. The Analog Output (1-5V) is saturated to the
configured Saturation Limit Low.
Adjust the Saturation Limit or the working
range if possible.
no effect
F098.034
Analog Output
Saturated
The analog output for the Primary Variable is beyond its High
scaling limit and no longer represents the true applied
process. The Analog Output (1-5V) is saturated to the
configured Saturation Limit High.
Adjust the Saturation Limit or the working
range if possible.
no effect