2.2 Specifications
Table 2.2: Specifications of the LD 810HSE Ex
FigureSpecification
18 V DC ... 32 V DC; SELV/PELV supply mandatoryPower supply
Typical input current is 200 mA; maximum is 1 A (considering the
rush-in current at switch-on).
Four FF-H1 channels, compliant with type 114 of the FF physical
layer profile
FF-H1
The Fieldbus voltage range is from 9 V DC ... 32 V DC. Preferred
value is 24 V DC.
IEEE 802.3 100BASE-TX/10BASE-TEthernet
-40 °CMinimum ambient
operating
temperature
-40 °C ... +85 °CStorage temperature
10 % ... 95 % (non-condensing)Relative humidity
Must not exceed 2,000 mAltitude
Indoor use only; no direct sunlightLocation
Conformal coating based on ANSI/ISA-S71.04 G3Coating
IEC/EN/UL 61010-1 Safety requirements for electrical equipment
for measurement, control and laboratory use - Part 1: General
requirements
Safety standard
IEC/EN/UL 61010-2-201 Safety requirements for electrical
equipment for measurement, control and laboratory use - Part
2-201: Particular requirements for control equipment (both with
CB scheme).
IP20Ingress protection
2PAA114135-610 24