EasyManua.ls Logo

ABB Ability 800xA Series - FF-H1 Interfaces

ABB Ability 800xA Series
124 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2.4.6 FF-H1 Interfaces
The LD 810HSE Ex provides 4 Foundation Fieldbus H1 interfaces. These interfaces are
named CH1 to CH4 and are used to connect an FF-H1 bus to the LD 810HSE Ex.
FF H1 Bus Line Channel 1
Table 2.9: H1 Channel 1 Connections
DescriptionSignalPinCH1
Fieldbus ++7
Fieldbus shieldS8
Fieldbus --9
FF H1 Bus Line Channel 2
Table 2.10: H1 Channel 2 Connections
DescriptionSignalPinCH2
Fieldbus ++10
Fieldbus shieldS11
Fieldbus --12
2PAA114135-610 35
2 Hardware Installation
2.4 Mounting and Dismounting

Table of Contents

Related product manuals