8. Plug in the power terminal block. The boot process and the download of the
configuration information take about 1 minute. For indication of proper operation as
a secondary device, refer to Status Indicators - LEDs on page 37.
Once the old LD 800HSE Ex is replaced by a new LD 810HSE Ex, the module name
will continue to appear as LD 800HSE Ex in Fieldbus Builder FOUNDATION™
Fieldbus. Only in the HSE Live List the module name will appear as LD810HSEEX
as shown in the screenshot below.
Figure 2.7: New LD 810HSE Ex in the HSE Live List
2PAA114135-610 50
2 Hardware Installation
2.9 Replacing a LD 800 HSE Ex by a New LD 810HSE Ex