• Check: compare the contents of the backup and current device state. Check fails
if the contents do not match, and passes if they match.
This view also shows the newly added, factory-reset devices, with IP address
192.168.2.10 (see bottom-most device in
Figure 30
). Any of the existing
backups can be deployed to this device. There can only be one factory-reset
device visible at a time, otherwise IP address conflict would occur.
Figure 30: Backup view
4.2 Disturbance identification
Disturbances and their causes can be identified by physical or WEB HMI indicator
LEDs: Ready, Start and Trip. During normal operation, the Ready LED is steady
green.
Table 10: Physical LED indications
LED
State Description
Start LED Green, steady Protection started
Start LED Green, flashing Protection function blocked
Trip LED Green, steady Protection operated
Ready LED Green, flashing Internal fault
Alarm LED Green, steady Programmable LED in alarm
state
1MRS758850 D IED operation
SSC600
Operation Manual
47