5.4 Correction procedures
5.4.1 Rebooting the software
In case of configuration data loss or any other file system error that prevents the
IED from working properly, the software can be rebooted. All default settings and
configuration files stored in the factory are restored.
Only a user with System Update right (refer to table Default roles-to-
rights in the Cyber Security Deployment Guideline) can reboot the
software.
1. Select IED Configuration> Configuration> General from the main menu
structure.
Figure 42: General menu
2. Enable parameter editing by selecting Enable Edit.
3. Reboot the software by changing the New Value field from Cancel to Activate.
4. Select Write to device to save changes to the IED's memory.
1MRS758850 D
Troubleshooting
SSC600
Operation Manual
63