EasyManua.ls Logo

ABB ACQ810 - Starting up ACS355 Drives with FMBA-01 Modbus RTU Adapter

ABB ACQ810
48 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Quickstart Guide
ABB PLC and drives integration using Modbus RTU
ModbusRTU‐15‐ PLCanddrivesintegration
StartingupACS355driveswithFMBA01ModbusRT
Uadapter
Minimumrequiredparametersettings(basedonfactorydefaultsettings)
Parameter Description Setting ApplicMacro
”AC500
MODBUS”*)
Comment
98.02 COMMPROTSEL STD
MODBUS
STD
MODBUS
Activatesfieldbusmodule
53.02 EFBSTATIONID [Address] 2 ModbusRTUnodeaddressofthedrive
53.03 EFBBAUDRATE 19.2kbit/s
(example)
19.2kbit/s Transferrateofthelink.Samebaudratemust
bedefinedintheModbusRTUmaster.
53.04 EFBPARITY 8NONE1
(example)
8NONE1 Parityandstopbits.Sameparityandstopbits
mustbedefinedintheModbusRTUmaster.
53.05 PROFILE ABBDRV
FULL
ABBDRV
FULL
Communicationprofile“ABBDrives”
53.10 ActualSpeed 101 101 Actualspeedfeedback
53.11 ActualValue2 105 303 Actualvalue2(e.gtorque105)(303=Status
Word1)
Drivepowerdownandpowerupforthenewfieldbussettingstotakeeffect!
10.01 EXT1COMMANDS COMM COMM Fieldbusinterfaceassourceforstartandstop
11.02 EXT1/EXT2SEL COMM COMM FieldbusinterfaceassourcetoswitchtoEXT2
11.03 REF1SELECT COMM COMM Fieldb usinterfaceassourceforspeed
reference
16.04 FAULTRESETSEL COMM COMM Fieldbusinterfaceassourceforfaultreset
Optionalparameterse
ttings
30.18 COMMFAULT
FUNC
[optional]
FAULT
Howthedrivereactstoafieldbus
communicationbreak.
30.19 COMMFAULTTIME [optional] Default:.3s Timebetweencommunicationbreakdetection
andtheselectedaction.
(11.05) REF1MAX [Scalemax] Maxspeed/frequencyscalingvalue(usedin
functionblock/visualizationinput
“SPEED_REF_MAX”).Mustbelessorequalto
driveparametermaxspeed/frequency.
*)inPar.99.02theApplicationMacrocanbesetto“AC500Modbus(10)”thentheparametersareautomatically
setasshown.

Other manuals for ABB ACQ810

Related product manuals