EasyManua.ls Logo

ABB ACS 311-1P1-1 - Page 38

ABB ACS 311-1P1-1
99 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
30 ACS 300 User’s Manual
Chapter 4 - Control Connections
Alternate
Alternate mode has both Start forward and Start reverse
inputs (+24 V). The drive is stopped if both inputs are con-
nected to 0 V or +24 V. Parameter PARAM SET has value 1.
Table 4-9 Alternate digital input functions.
Figure 4-6 Alternate switch S1 selection.
Table 4-10 Start functions for Alternate.
Digital
input
Function Notes
DI1 Start Forward Connect +24 V DC to Start Forward/
Reverse
refer to Table 4-10.
DI2 Start Reverse
DI3 CS1 Constant speed (=CS) selection,
refer to Table 4-11.
DI4 CS2
DI5 ACC2/DEC2 0 V = ramp 1 and +24 V DC = ramp 2
DI1 DI2 Result
0 0 Drive stopped
1 0 Run forward
0 1 Run reverse
1 1 Drive stopped
Alternate
OFF ON
0 1
A
B
C

Related product manuals