ACS 300 User’s Manual 45
Chapter 7 - Drive Parameters
Parameter Tables The following parameter tables list the drive parameters,
adjustment ranges and default values. A space is provided for
recording customer settings. The tables include a short
description of each parameter and lists the page numbers
where a detailed explanation can be found.
Note! The factory setting for display language is English, refer
to Page 1 parameter LANGUAGE for display language selec-
tion. Parameters marked with (0) can only be altered with the
ACS 300 stopped otherwise START IS ACTIVE message is
displayed. (L) indicates that the parameter can be altered in
Local control mode only.
Table 7-1 Page 1 Drive parameters and their factory settings.
Code Parameter Range Default Customer Page Description
PAGE 1 (*P2) Display only –– 48Press to change to page 2
101 OUTPUT f Display only 48 Frequency to motor
102 REF FREQ/
LOC FREQ (L)
f
MIN
– f
MAX
0 Hz 49 Frequency reference from remote or
control panel
103 SPEED Display only 49 Calculated motor speed
104 OUTPUT I Display only 49 Motor current
105 COPY Exit/Read/Write/
Set Factory Def.
Exit 49 Transfers all settings to and from
panel
106 MIN FREQ 0.0 – 200/500 Hz
1)
0.0 Hz 49 Reference input minimum frequency
107 MAX FREQ 0.0 – 200/500 Hz
1)
50 Hz 49 Maximum output frequency
108 ACC 1 0.1 – 1800 s
2)
3 s 49 Time for Ref Min f - Ref Max f
acceleration ramp
109 DEC 1 0.1 – 1800 s
2)
3 s 49 Time for Ref Max f - Ref Min f
deceleration ramp
110 ACC 2 0.1 – 1800 s
2)
3 s 49 Time for Ref Min f - Ref Max f
acceleration ramp
111 DEC 2 0.1 – 1800 s
2)
3 s 49 Time for Ref Max f - Ref Min f
deceleration ramp