32 ACS 300 User’s Manual
Chapter 4 - Control Connections
Motor Potentiometer
Motor Potentiometer mode has motor potentiometer func-
tion programmed to digital inputs 3 and 4. Parameter
PARAM SET has value 1. Table 4-14 shows the functions of
the digital inputs when in Motor Potentiometer mode.
Table 4-14 Motor Potentiometer digital input functions.
If you select Start, ACS 300 is set to minimum frequency. If
you use Reverse, the drive will continue with a frequency
that is the negative value of the valid reference frequency.
The ACS 300 accelerates/decelerates using Page 1 param-
eters ACC 1/ DEC 1 when changing rotation direction.
Acceleration from 0 Hz to MIN FREQ is also done with ramp
1.
Note! AI is disabled when Motor potentiometer control mode
is selected.
Note! STOP command (power off) resets parameter REF
FREQ.
Digital input Function Notes
DI1 Start Connect +24 V DC to Start
DI2 Reverse Connect +24 V DC to Reverse
DI3 Increment fr. Connect +24 V DC to increment fr. (ramp
2)
DI4 Decrement fr. Connect +24 V DC to decrement fr.
(ramp 2)
DI5 CS1 Connect +24 V DC to select constant
speed 1