ACS 300 User’s Manual 47
Chapter 7 - Drive Parameters
Table 7-3 Page 3 Drive parameters and their factory settings.
210 A. OUT None/Out Freq/Ref
Freq/Motor Curr
None 57 Analog output function selection
211 A. OUT OFFS 0 mA/4 mA 0 mA 57 Analog output minimum
212 SWITCH f 1.0 – 16.0 kHz 4 kHz 58 Switching frequency
213 CRIT f1L 0.0 – 200/500 Hz
1)
0.0 Hz 58 Critical frequency 1 start
214 CRIT f1H 0.0 – 200/500 Hz
1)
0.0 Hz 58 Critical frequency 1 end
215 CRIT f2L 0.0 – 200/500 Hz
1)
0.0 Hz 58 Critical frequency 2 start
216 CRIT f2H 0.0 – 200/500 Hz
1)
0.0 Hz 58 Critical frequency 2 end
217 IR-COMP Off/0.1 – 60 V/ Auto Off 60 Low speed torque boost value
218 DC BRAKE 0 – 250 s 3 s 61 Duration of DC braking/DCHold
219 U/f RATIO (0) Linear/Square/Optim Linear 61 Voltage to frequency ratio
220 RESTART # Off/1 - 10/Cont Linear 62 Nr. of start attempts after fault
221 TEMP LIM Off/1 to 500 Hz Off 62 Motor Thermal Protection
222 Motor I 0.5 to 1.5* I
N
I
N
63 I
NMOT
for thermal protection
223 DIR FWD/REV: FWD only FEW?REV 64 Reverse lock-out
224 AI-FAULT Enable/Disable Enable 64 AI fault if AI < 2 V/ 4mA
225 1. RELAY 1 - 11 1 64 Relay 1 function selection
226 2. RELAY 1 - 11 7 64 Relay 2 function selection
227 F SUPERV 0.0 to 500 Hz 66 Relay function output freq. limit
Code Parameter Range Default Customer Page Description
Code Parameter Range Default Customer Page Description
Page 3 (*P4) – – – 66 Press to change to page 4
701 DC HOLD 0/ 1/ 2 0 66 None/ Normal/ Strong DC hold
702 PARAM SET 1/ 2 1 67 Enables/disables extended I/O
configuration/ Parameter set 2
703 PI-GAIN (0) 0 - 800 % 0 68 PI-Controller Gain selection
704 PI-ITIME 0.0 - 320.0 s 0 68 PI-Controller I-time selection
705 PI-SCMIN -999.9 - 999.9% 0 69 Minimum scaling factor of Actual
value
706 PI-SCMAX -999.9 - 999.9% 100 69 Maximum scaling factor of Actual
value