90 ACS 400 Users Manual
2107 START INHIBIT
Start inhibit control. Start inhibit means that a pending start command is ignored when:
fault is reset, or
Run Enable activates while start command is active, or
mode change from local to remote takes place, or
mode change from remote to local takes place, or
when switching from
EXT1 to EXT2 takes place, or
when switching from
EXT2 to EXT1 takes place
0 =
OFF
Start inhibit control disabled. Drive will start after fault is reset, Run Enable is activated or mode is changed
while there is a pending start command.
1 =
ON
Start inhibit control enabled. Drive will not start after fault is reset, Run Enable is activated or mode is
changed. In order to start the drive again, give start command anew.