Loading...
Output ratingsInput
with
choke
Input
cur-
rent
ACS180-04...
Frame
size
Heavy-duty useLight-duty useMax.
current
P
Hd
I
Hd
P
Ld
I
Ld
I
max
I
1
I
1
hpAhpAAAA
R41544
15/20
1)
50.279.25559.6-055A-2
3-phase
U
n
= 440 ... 480 V
R00.51.10.751.62.21.31.9-01A8-4
R00.751.612.13.31.62.4-02A6-4
R012.11.534.32.13.5-03A3-4
R11.5323.55.92.84.6-04A0-4
R123.534.87.23.86.9-05A6-4
R134.8361059.2-07A2-4
R136.357.6136.710.3-09A4-4
R257.67.51116.91114.8-12A6-4
R27.511101422.71420.3-17A0-4
R31014152130.62126.6-25A0-4
R315212027452733.9-033A-4
R42027253457.63441.3-038A-4
R42534304068.44046.9-045A-4
R430423042814246.9-050A-4
1)
15 hp at 208...230 V input. 20 hp at 240 V input.
Definitions
The heavy duty ratings are valid at a surrounding air temperature of 50 °C (122 °F)
and the light duty ratings are valid at a surrounding air temperature of 40 °C
(104 °F) with the default drive switching frequency of 4 kHz (parameter 97.01), and
with an installation altitude below 1000 m (3281 ft).
U
n
Nominal supply voltage. For input voltage range U1, refer to Electrical
power network specification (page 129).
I
1
Nominal input current with typical motor power P
n
. Continuous rms
input current, for dimensioning cables and fuses.
I
max
Maximum output current. Available for two seconds at start.