Bussmann type
Voltage
rating
I
2
t
Nominal
current
Min. short-
circuit cur-
rent
1)
Input
current
ACS180-04...
VA
2
sAAA
FWP-50G14F69022005065621.2-17A5-2
FWP-80G22F69054488040027.2-25A0-2
FWP-100G22F690665010050435-033A-2
FWP-150A7001170016080048-048A-2
FWP-150A7001170016080060-055A-2
3-phase
U
n
= 380 ... 415 V
FWP-20G14F69017020472.8-01A8-4
FWP-20G14F69017020603.6-02A6-4
FWP-20G14F69017020874.6-03A3-4
FWP-25G14F690333251166.3-04A0-4
FWP-25G14F690333251749-05A6-4
FWP-32G14F6906793223012-07A2-4
FWP-32G14F6906793225813-09A4-4
FWP-50G14F69022005044017.4-12A6-4
FWP-50G14F69022005056025.2-17A0-4
FWP-80G22F69036008040031.8-25A0-4
FWP-100G22F690665010050440.9-033A-4
FWP-125A700730012564049-038A-4
FWP-150A7001170016080055.7-045A-4
FWP-150A7001170016080055.7-050A-4
1)
Minimum permitted short-circuit current of the electrical power network
UL (NEC) fuses
The UL listed fuses in the table are the required branch circuit protection. Fuses
must be provided as part of the installation.
Type
Buss-
mann
type
Voltage
rating
Nominal
current
Min. short-cir-
cuit current
Input
current
ACS180-04...
VAAA
1-phase
U
n
= 208 ... 240 V
UL class TJJN-63006624.8-02A4-1
112 Technical data