Free space requirements
SidesBelowAboveFrame size
inmminmminmm
250
1)
375375R0
00375375R1-R4
Note: 1) If ambinet temperature is below 40°C (104 F), modules can be installed
side-by-side.
Losses, cooling data and noise
Drives with frame size R0 have natural convection cooling. Drives with frame size
R1…R4 have a cooling fan. The air flow direction is from bottom to top.
Note: power losses are given for nominal supply voltage, default switching
frequency, and rated output current/power. Changing these factors may result in
increased power losses.
Frame
size
NoiseAir flow
Typical power loss
1)
ACS180-04...
dB(A)CFMm
3
/hBTU/hW
1-phase
U
n
= 208 ... 240 V
R0---8224-02A4-1
R0---13639.9-03A7-1
R0---15645.6-04A8-1
R152162724571.8-06A9-1
R1521627418122.4-07A8-1
R152162726878.6-09A8-1
R26277130445130.5-12A2-1
3-phase
U
n
= 208 ... 240 V
R0---8926-02A4-2
R0---13740.1-03A7-2
R0---16047-04A8-2
R152162720961.2-06A9-2
R152162721964.2-07A8-2
R152162725273.9-09A8-2
R26277130581170.3-15A6-2