EasyManua.ls Logo

ABB ACS180-04S-03A7-1 - Page 136

ABB ACS180-04S-03A7-1
192 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Transportation in
the protective
package
Storage in the
protective pack-
age
Operation installed for sta-
tionary use
Requirement
-40 +70 °C-40 +70 °CFor frame size R0:Surrounding air tem-
perature at heavy
duty rating
(-40 158 °F)(-40 158 °F)-10 +50 °C (14 122 °F)
without derating.
Temperature above 50 °C
not allowed.
For frame sizes R1...R4:
-10 +50 °C (14 122 °F)
without derating.
50 60 °C (122 140 °F)
with derating.
No frost allowed.
For frame size R0:Surrounding air tem-
perature at light duty
rating
-10 +40 °C (14 104 °F)
without derating.
+40 +50 °C (104 ... 122 °F)
with derating.
For frame sizes R1...R2:
-10 +40 °C (14 ... 104 °F)
without derating.
+40 +60 °C (104 ... 104 °F)
with derating.
For frame sizes R3...R4:
-10 +50 °C (14 ... 122 °F)
without derating.
+50 +60 °C (122 ... 140 °F)
with derating.
No frost allowed.
<95% (IEC 60068-2-78) without condensationRelative humidity
Class 2C2Class 1C2Class 3C2Contamination levels
(IEC 60721-3-3)
Class 2S2Class 1S2Class 3S2
--Class 3M4Sinusoidal vibration
(IEC 61800-5-1 to
comply with EN
50178)
According to ISTA
1A.
According to ISTA
1A.
Not allowedShock
(EN 60068-2-31 to
comply with EN
50178)
Max. 100 m/s2
(330 ft/s2), 11 ms.
Max. 100 m/s2
(330 ft/s2), 11 ms.
136 Technical data

Table of Contents

Related product manuals