EasyManua.ls Logo

ABB ACS180-04S-03A7-1 - Page 70

ABB ACS180-04S-03A7-1
192 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
R3
M4x10, 2x
3. Strip the motor cable.
4. Ground the motor cable shield under the grounding clamp.
5. Twist the motor cable shield into a bundle, mark it with yellow-green and
connect it to the grounding terminal.
6. Connect the phase conductors of the motor cable to the T1/U, T2/V and T3/W
motor terminals.
7. For frame sizes R2-R4, if you use a brake resistor, connect the brake resistor
cable to the R- and UDC+ terminals. Use shielded cable and ground the shield
under the grounding clamp (360-degree grounding).
8. Strip the input power cable.
70 Electrical installation

Table of Contents

Related product manuals