Typical power cables
US
2)
IEC
1)
ACS880-
04-…
Al cable typeCu cable typeAl cable typeCu cable type
AWG/kcmilAWG/kcmilmm
2
mm
2
U
n
= 400 V
2×700 MCM or 3×350 MCM2×500 MCM or 3×250 MCM3×(3×150)3×(3×95)505A-3
3×400 MCM or 4×250 MCM2×600 MCM or 3×300 MCM3×(3×185)3×(3×120)585A-3
3×400 MCM or 4×250 MCM2×700 MCM or 3×350 MCM3×(3×240)3×(3×150)650A-3
3×500 MCM or 4×300 MCM3×500 MCM or 4×300 MCM4×(3×185)3×(3×185)725A-3
3×700 MCM or 4×500 MCM3×600 MCM or 4×400 MCM4×(3×240)3×(3×240)820A-3
4×500 MCM3×600 MCM or 4×400 MCM4×(3×240)3×(3×240)880A-3
U
n
= 500 V
2×600 MCM or 3×300 MCM2×400 MCM or 3×4/03×(3×150)3×(3×95)460A-5
2×700 MCM or 3×350 MCM2×500 MCM or 3×250 MCM3×(3×150)3×(3×95)503A-5
3×500 MCM or 4×300 MCM2×600 MCM or 3×300 MCM3×(3×185)3×(3×120)583A-5
3×600 MCM or 4×400 MCM2×700 MCM or 3×350 MCM3×(3×240)3×(3×150)635A-5
3×600 MCM or 4×400 MCM3×500 MCM or 4×300 MCM4×(3×185)3×(3×185)715A-5
4×500 MCM3×600 MCM or 4×400 MCM4×(3×240)3×(3×240)820A-5
4×500 MCM3×600 MCM or 4×400 MCM4×(3×240)3×(3×240)880A-5
U
n
= 690 V
2×350 MCM or 3×4/02×300 MCM or 3×3/02×(3×120)2×(3×95)330A-7
2×400 MCM or 3×4/02×300 MCM or 3×3/02×(3×120)2×(3×95)370A-7
2×500 MCM or 3×250 MCM2×350 MCM or 3×4/02×(3×120)2×(3×95)430A-7
2×600 MCM or 3×300 MCM2×400 MCM or 3×4/03×(3×150)3×(3×95)470A-7
2×700 MCM or 3×350 MCM2×500 MCM or 3×250 MCM3×(3×185)3×(3×120)522A-7
3×500 MCM or 4×300 MCM2×600 MCM or 3×300 MCM3×(3×185)3×(3×150)590A-7
3×500 MCM or 4×300 MCM2×700 MCM or 3×350 MCM3×(3×240)3×(3×150)650A-7
3×600 MCM or 4×400 MCM3×500 MCM or 4×300 MCM4×(3×185)3×(3×185)721A-7
1)
The cable selection is based on max. 9 cables laid on a cable ladder side by side, three ladder type trays one on top
of the other, ambient temperature 30 °C (86 °F) PVC insulation, surface temperature 70 °C (158 °F) (EN 60204-1 and
IEC 60364-5-52). For other conditions, select the cables according to local safety regulations, appropriate input
voltage and the load current of the drive.
2)
The cable selection is based on NEC Table 310-16 for copper wires, 75 °C (167 °F) wire insulation at 40 °C (104 °F)
ambient temperature. Not more than three current-carrying conductors in raceway or cable or earth (directly buried).
For other conditions, dimension the cables according to local safety regulations, appropriate input voltage and
the load current of the drive.
Terminal and entry data for the power cables
4 × (3 × 240) mm
2
or 4 × (3 × 500 MCM)Maximum accepted
cable size
M12Screw size for connect-
ing busbars to the drive
module input and output
busbars
50…75 N·m (37…55 lbf·ft)Tightening torque
266 Technical data and references