AC 80 User’s Manual 4-23
Essential Settings
Only the user-adjustable settings are represented. (The tables also
include the information readable from the output terminals.) For more
details, see the
AC 80 PC Elements Reference Manual.
PANBUS
Base part:
Communication:
PANC
NAME Max. 20 characters
ACT 0 = Spare element
1 = Active element
NET 1
MASTER 1
SPEED Max. 19200
CHLEN 8
STOPBITS 1 (Can also be 1.5 or 2)
PARITY NONE
LINESTAB 1
CARRDEL 0
MAXRETR 2 (Max 20)
CHARTOUT 2
TURNTIME 1000
C1 (Call Parameter) Number of DATs (0 to 72).
C2 (Call Parameter) 0 = Spare element
1 = Active element
PAN_ID Station address of the control panel.
LOGNR ID number of event logger.
RESET 0
CNTRL
See the
AC 80 PC Elements Reference Manual.
DAT