EasyManua.ls Logo

ABB Advant Controller 80

ABB Advant Controller 80
84 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
AC 80 User’s Manual 4-23
Essential Settings
Only the user-adjustable settings are represented. (The tables also
include the information readable from the output terminals.) For more
details, see the
AC 80 PC Elements Reference Manual.
PANBUS
Base part:
Communication:
PANC
NAME Max. 20 characters
ACT 0 = Spare element
1 = Active element
NET 1
MASTER 1
SPEED Max. 19200
CHLEN 8
STOPBITS 1 (Can also be 1.5 or 2)
PARITY NONE
LINESTAB 1
CARRDEL 0
MAXRETR 2 (Max 20)
CHARTOUT 2
TURNTIME 1000
C1 (Call Parameter) Number of DATs (0 to 72).
C2 (Call Parameter) 0 = Spare element
1 = Active element
PAN_ID Station address of the control panel.
LOGNR ID number of event logger.
RESET 0
CNTRL
See the
AC 80 PC Elements Reference Manual.
DAT
PAR

Table of Contents

Related product manuals