ControlMaster CM15 and CMF160
Universal process indicator
1
/8 DIN 4 Installation
16 IM/CM/I–EN Rev. P
4.3.2 CMF160 Indicator
ControlMaster CMF160 can be panel-, pipe- or
wall-mounted. For NEMA4X protection, a panel thickness of
6 mm (0.236 in.) is required. (For pipe-mount details, see Fig.
4.5, page 13. For wall-mount details, see Fig. 4.6, page 13.)
To panel-mount the ControlMaster CMF160 indicator:
1. Cut a hole of the correct size for the controller in the
panel (see page 11 for cut-out dimensions).
Referring to Fig. 4.9:
2. Insert the controller B into the panel cut-out C.
3. Position the panel clamps D at each side of the case
against the panel.
4. Tighten each panel clamp anchor screw E until both
panel clamps D are secured against the panel
(torque 0.5 to 0.6 Nm [4.42 to 5.31 lbf/in.]).
Note. It may be necessary to cut a notch out of
the panel at position A to accommodate the
small rod on the lower face of the indicator B.
Note. Do not overtighten the screws.
Fig. 4.9 Mounting Details – CMF160 Indicator