Configuring 4–20 mA input channels 23
Setting sensor scaling
Since this input channel uses the 4–20 loop standard, it is necessary to set the values for the 4 mA and
20 mA currents. You enter these values in the 4 mA value and 20 mA value fields.
For example, a temperature sensor will output a signal from 4-mA to 20mA for a corresponding
temperature range of –50°C to 150°C.
You can enter such values in the Sensor scaling section.
Figure 20 Entering sensor scaling values
Check the Enabled box bellow Sensor scaling to activate this function.
Click Apply at the bottom of the page to save your changes.
Setting post-processing channel values
With the CoreSense M10, it is possible to add additive and/or multiplicative correction factors to raw
sensor data. In CoreSense M10, multiplicative factors are known as slopes and additive factors, as
offsets.
For example, a slope of 1.1 applied to a temperature of 100 degrees brings the raw sensor measurement
to 110 degrees.
As for offsets, an offset of –5 applied to a temperature of 100 degrees brings the raw sensor
measurement to 95 degrees.
You can enter such values in the Post-processing(opt) section.
Figure 21 Entering post-processing values
Click Apply at the bottom of the page to save your changes.