IEC 61850 C83
Ed. Services A A: TP/M C Client (C) Server (S) Comments
T2 1,2 Time accuracy
of internal clock
Unspecified TL (ms) (low accuracy), T3 < 7)
(only Ed2)
T0 (ms) (<= 10 ms), 7 <= T3 < 9
T1 (µs) (<= 1 ms), 10 <= T3 < 13
T2 (µs) (<= 100 µs), 13 <= T3 < 15
T3 (µs) (<= 25 µs), 15 <= T3 < 18
T4 (µs) (<= 25 µs), 15 <= T3 < 18
T5 (µs) (<= 1 µs), T3 >= 20
T3 1,2 Supported TimeStamp
resolution
2
-24
seconds Nearest value of 2
-n
in seconds
(number 0 to 24)
TICS Mandatory IntOp TISSUES
The table below gives an overview of the implemented IntOp Tissues.
NOTICE
Tissue 49, 190, 191, 275 and 278 are part of tissue 453, all other technical tissues in the table are
mandatory if applicable.
Editorial tissues are marked as “NA”.
Final proposal on tissue 45 is not defined yet
Part TISSUE No. Description Im p l . Y/ N A
8-1 116 GetNameList with empty response? Y
165 Improper Error Response for GetDataSetValues Y
183 GetNameList error handling Y
246 Control negative response (SBOns) with LastApplError NA
545 Skip file directories with no files NA
7-4 None
7-3 28 Definition of APC NA
54 Point def xVal, not cVal NA
55 Ineut = Ires? NA
63 mag in CDC CMV NA
65 Deadband calculation of a Vector and trigger option NA
219 operTm in ACT NA
270 WYE and DEL rms values NA
1199 BCR NA