C64 User Guide
ID ED Description Value/Clarification
As8 1,2 What is the maximum start up time after a power supply
interrupt
5 minutes
As9 1,2 Does this device function only as test equipment?
(test equipment need not have a non-volatile configuration; but
it cannot be part of the substation automation system)
No
PIXIT for Server Model
ID ED Description Value/Clarification
Sr1 1,2 Which analogue value (MX) quality bits are supported (can be set by
server)
Validity:
Good Y
Invalid Y
Reserved N
Questionable Y
Overflow N
OutofRange N
BadReference N
Oscillatory N
Failure Y
OldData N
Inconsistent N
Inaccurate N
Source:
Process Y
Substituted Y
Test N
OperatorBlocked N