EasyManua.ls Logo

ABB CoreSense M10 - PIXIT for Data Set Model; PIXIT for Substitution Model

ABB CoreSense M10
108 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
IEC 61850 C65
ID ED Description Value/Clarification
Sr2 1,2 Which status value (ST) quality bits are supported (can be set by
server)
Validity:
Good Y
Invalid Y
Reserved N
Questionable Y
Overflow N
BadReference N
Oscillatory N
Failure Y
OldData N
Inconsistent N
Inaccurate N
Source:
Process Y
Substituted Y
Test N
OperatorBlocked N
Sr3 - What is the maximum number of data object references in one
GetDataValues request
Deprecated
Sr4 - What is the maximum number of data object references in one
SetDataValues request
Deprecated
Sr5 1 Which Mode values are supported On Y
[On-]Blocked N
Test N
Test/Blocked N
Off N
PIXIT for Data Set Model
ID ED Description Value/Clarification
Ds1 1 What is the maximum number of data elements in
one data set (compare ICD setting)
Only one non-configurable dataset containing
all DO.
Ds2 1 How many persistent data sets can be created by
one or more clients
(this number includes predefined datasets)
Only one non-configurable dataset containing
all DO. Data set creation is not supported.
Ds3 1 How many non-persistent data sets can be created
by one or more clients
Data set creation is not supported.
PIXIT for Substitution Model
ID ED Description Value/Clarification
Sb1 1 Are substituted values stored in volatile memory Substitution is not supported.