ABB CoreSense M10 - ACSI Service Conformance Test

ABB CoreSense M10
108 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
C80 User Guide
Client/ Subscriber Server/ Publisher Value/ Comments
If SVC (B41/42) is supported
M14 Multicast SVC N
M15 Unicast SVC N
For all IEDs
M16 Time Y Time source with required accuracy
shall be available.
Only Time Master are SNTP (Mode 4
response) time server.
All other Client / Server devices
require SNTP (Mode 3 request) clients
Y = service is supported
N or empty = service is not supported
ACSI Service Conformance Test
The ACSI service conformance statement is defined below (depending on the statements in ACSI Basic
Conformance Statement and in ACSI Models Conformance Statement).
Ed. Services A A: TP/M C Client (C) Server (S) Comments
Server
S1 1,2 GetServerDirectory
(LOGICAL-DEVICE)
TP Y
Application Association
S2 1,2 Associate Y
S3 1,2 Abort Y
S4 1,2 Release Y
Logical Device
S5 1,2 GetLogicalDeviceDirectory TP Y
Logical Node
S6 1,2 GetLogicalNodeDirectory TP Y
S7 1,2 GetAllDataValues TP Y
Data
S8 1,2 GetDataValues TP Y
S9 1,2 SetDataValues TP Y
S10 1,2 GetDataDirectory TP Y
S11 1,2 GetDataDefinition TP Y
Data Set
S12 1,2 GetDataSetValues TP Y
S13 1,2 SetDataSetValues TP N
S14 1,2 CreateDataSet TP N
S15 1,2 DeleteDataSet TP N
S16 1,2 GetDataSetDirectory TP Y