IEC 61850 C79
Client/ Subscriber Server/ Publisher Value/ Comments
Reporting
M7 Buffered report control N
M7.1 sequence-number N
M7.2 report-time-stamp N
M7.3 reason-for-inclusion N
M7.4 data-set-name N
M7.5 data-reference N
M7.6 buffer-overflow N
M7.7 entryID N
M7.8 BufTm N
M7.9 IntgPd N
M7.10 GI N
M7.11 conf-revision N
M8 Unbuffered report control Y
M8.1 sequence-number Y
M8.2 report-time-stamp Y
M8.3 reason-for-inclusion Y
M8.4 data-set-name Y
M8.5 data-reference Y
M8.6 BufTm Y
M8.7 IntgPd Y
M8.8 GI Y
M8.9 conf-revision Y
Logging
M9 Log control N
M9.1 IntgPd N
M10 Log N
M11 Control Y
M17 File Transfer N
M18 Application association Y
M19 GOOSE Control Block N
M20 Sampled Value Control Block N
If GSE (B31/32) is supported
M12 GOOSE N
M13 GSSE N Deprecated in Edition 2
Y = service is supported
N or empty = service is not supported