ABB CoreSense M10 - DNP3 Pointmap

ABB CoreSense M10
108 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
B60 User Guide
Pointmap1 2 3 4 5
Analog input Binary input
Name Point index Unit Name Point index
4–20 mA
6
input 1 10 mA n/a n/a
4–20 mA input 2 11 mA n/a n/a
4–20 mA input 3 12 mA n/a n/a
4–20 mA input 4 13 mA n/a n/a
CH4 23 ppm CH4_Lev_Warn 15
CH4_Roc_Day 24 ppm/day CH4_Lev_Crit 16
Reserved 25 CH4_Roc_Warn 17
Reserved 26 CH4_Roc_Crit 18
CO2 27 ppm CO2_Lev_Warn 19
CO2_Roc_Day 28 ppm/day CO2_Lev_Crit 20
Reserved 29 CO2_Roc_Warn 21
Reserved 30 CO2_Roc_Crit 22
CO 31 ppm CO_Lev_Warn 23
CO_Roc_Day 32 ppm/day CO_Lev_Crit 24
Reserved 33 CO_Roc_Warn 25
Reserved 34 CO_Roc_Crit 26
C2H2 35 ppm C2H2_Lev_Warn 27
C2H2_Roc_Day 36 ppm/day C2H2_Lev_Crit 28
Reserved 37 C2H2_Roc_Warn 29
Reserved 38 C2H2_Roc_Crit 30
C2H4 39 ppm C2H4_Lev_Warn 31
C2H4_Roc_Day 40 ppm/day C2H4_Lev_Crit 32
Reserved 41 C2H4_Roc_Warn 33
Reserved 42 C2H4_Roc_Crit 34
C2H6 43 ppm C2H6_Lev_Warn 35
C2H6_Roc_Day 44 ppm/day C2H6_Lev_Crit 36
1 Event class is None
2 For binary inputs, name for state when value is zero = off.
3 For binary inputs, name for state when value is one = on.
4 Rate-of-change (RoC) is calculated on a 24-hour time period.
5 For analog inputs, the multiplier is always 0.1 and the offset, 0
6 4–20 mA inputs' function is scaled by 100