102
Service
3ADW000488R0101 DCS880 Service manual e a
Current transformers for sizes H6 and H7
Type:
LT 2032.
Ordering number:
3ADT751010P0001.
Rated primary current:
3000 A
AC
.
Rated secondary current:
1.2 A
AC
.
Ratio:
2500 : 1.
Magnetic overload capacity for a short time:
3 times rated primary current.
Maximum rated voltage:
1500 V
AC
.
Maximum test voltage:
5000 V
AC
for less than 3 seconds.
Dimensions:
In mm, see figure below.
Weight:
1.7 kg.
Maximum ambient (e.g. cooling air) temperature at rated current:
55°C.
Maximum conductor (wire/busbar) temperature at rated current:
90°C.