107
Service
3ADW000488R0101 DCS880 Service manual e a
DCS880 firmware download
General
This file describes how to download firmware into the SDCS-CON-H01.
Download SDCS-CON-H01 firmware using the Drive loader 2.x
Installation
Double click on Drive loader 2.x
setup.exe.
Follow the setup instructions.
This installs the Drive loader 2.x.
Prepare firmware download
The firmware download is setting all parameters back to default. Before starting, make a parameter
backup using either the control panel or Drive composer.
The firmware download deletes all application programs. Make sure that it is possible to re-load the
application programs.
The firmware download is done via a
USB port and the control panel.
Firmware download
Make sure:
The drive composer is closed.
The DCS880 is done with booting (energized, auxiliary voltage is on).
The control panel is only connected to one DCS880.
Open the Drive loader 2.x by double click.