Safe Torque Off (STO)
3ADW000488R0101 DCS880 Service manual e a
Evaluation of the graph and observations
At the start of the procedure the monitor
value of 31.98 STO actual status must be
0xF.
After opening the STO circuit the value of
31.98 STO actual status must be 0xA.
After about 500 ms the value of 31.98 STO
actual status must be 0x2 or 0x8.
Shortly after the value of 31.98 STO actual
status must be 0x0.
Compare the values of 31.94 STO time 1
and 31.95 STO time 2. Their values must
be within 20 ms of each other and within
Document and sign the STO revalidation test which verifies that the safety function is safe and
accepted for operation in the machine log book.