13
Introduction to this manual
3ADW000488R0101 DCS880 Service manual e a
Current ratings
Unit size
2-Q rated current
DCS880-S01 [A
DC
]
4-Q rated current
DCS880-S02 [A
DC
]
Supply voltage [V
AC
]
400
525
600
690
800
990
1200
H1
20
25
X
X
45
50
X
X
65
75
X
X
90
100
X
X
H2
135
150
X
X
180
200
X
X
225
250
X
X
270
300
X
X
H3
290
320
X
315
350
X
X
405
450
X
X
470
520
X
X
H4
590
650
X
610
680
X
X
740
820
X
X
900
1000
X
X
H5
1190
1190
X
X
H6
900
900
X
X
1200
1200
X
X
1500
1500
X
X
X
X
2000
X
X
X
X
2000
X
X
H7
1900
1900
X
2050
2050
X
X
X
2500
2500
X
X
X
X
X
3000
3000
X
X
X
X
X
H8
2050
2050
X
2600
2600
X
X
3300
3300
X
X
X
X
X
X
X
4000
4000
X
X
X
X
X
X
X
4800
4800
X
X
X
5200
5200
X
X
1190 A
DC
for 35°C and 1140 A
DC
for 40°C ambient temperature.