Preventive Maintenance
3ADW000488R0101 DCS880 Service manual e a
6 years preventive maintenance
Following additional actions have to take place:
Replace the cooling fans of units H5 and H6:
Exchange cooling fan size H5.
Exchange cooling fan size H6.
The manufacturer’s estimation for the operational time of the cooling fans is:
R2E250-RB 40,000 hours at 40°C.
The mayor problem is the failure of the bearings. The cooling fans are used in:
DCS880-S0b-1190-dd
H5
R2E250-RB
230 V
DCS880-S0b-0900-dd ...
DCS880-S0b-2000-dd
H6
Aging of the components result in:
Increased vibration due to the imbalance of the cooling fan (can last for several months).
Increased temperature due to the stopped cooling fan (drive trips with overtemperature).
Replace the cooling fans of units H1 … H4.
Exchange the cooling fan size H1 (one fan).
Exchange the cooling fan sizes H2 … H3 (two fans).
Exchange the cooling fan size H3 (four fans).
Exchange the cooling fan size H4.
The manufacturer’s estimation for the operational time of the classic cooling fans is:
3110UL: 70,000 hours at 25°.
AFB122: 100,000 hours at 25°.
W2E200: 45,000 hours at 60°C.
W2E250: 40,000 hours.
The mayor problem is the failure of the bearings. The cooling fans are used in:
DCS880-S0b-0045-dd ...
DCS880-S0b-00100-dd
H1
1 x 3110UL
24 V internal
DCS880-S0b-0135-dd ...
DCS880-S0b-0300-dd
H2
2 x AFB122
24 V internal
DCS880-S0b-0315-dd ...
DCS880-S0b-0450-dd
H3
2 x 3110UL
2 x AFB122
24 V internal
DCS880-S0b-0610-dd ...
DCS880-S0b-0820-dd
H4
1 x W2E200
230 V
1 x W2E200
115 V (plus code E171)
DCS880-S0b-0900-dd ...
DCS880-S0b-1000-dd
1 x W2E250
230 V
1 x W2E250
115 V (plus code E171)
Aging of the components result in:
Increased vibration due to the imbalance of the cooling fan (can last for several months).
Increased temperature due to the stopped cooling fan (drive trips with overtemperature).
Check the flat cables and their connections.