46  Start-up       
10.08 FAULT RESET 
SEL
P.FBA MAIN CW.8  Selects the fieldbus interface as 
the source for the fault reset 
signal.
24.01 SPEED REF1 SEL FBA REF1 Selects the fieldbus reference 1 
as the source for speed 
reference 1.
32.01 TORQ REF1 SEL FBA REF1 Selects the fieldbus reference 1 
as the source for torque 
reference 1.
34.01 EXT1/EXT2 SEL C.False Selects that the external control 
location is always EXT1.
34.02 EXT1 MODE 
1/2SEL
C.False Selects the source for the 
default drive control mode 
selection.
34.03 EXT1 CTRL 
MODE1
Speed
Torque
Position
Synchron
Selects the default (power up) 
drive control mode. 
3)
For more information on using 
the position control mode, see 
ACSM1 motion control program 
firmware manual 
(3AFE68848270 [English]).
57.09 KERNEL SYNC 
MODE
FBSync See section Drive 
synchronization on page 92.
60.02 POS AXIS MODE Linear
Rollover
Selects whether to have 
continuous position data range 
or position data range with one 
revolution wrap-around.
4)
60.09 POS 
RESOLUTION
10…24 Selects the internal resolution of 
the position data between the 
module and the drive, not at the 
master.
5)
60.05 POS UNIT Revolution Mandatory setting
60.10 POS SPEED UNIT u/s Mandatory setting
62.01 HOMING 
METHOD
CAN Method 1 …
CAN Method35
Selects the homing method. The 
homing method needs to be 
selected if one intends to use 
homing. 
For more information on the 
homing methods, see ACSM1 
motion control program firmware 
manual (3AFE68848270 
[English]).
Drive parameter Setting for ACSM1 
drives
Description